Home - What is Bio-Sure® - Installation Procedure - Quantity Calculator - Scale & Corrosion - Product Performance
Customers - Testimonials - AgriQuality & MSDS - Servicing Reports & Procedures - Contact - Purchase

A SIMPLE ANSWER TO COOLING TOWER WATER TREATMENT

Independant Performance Data undertaken at Dunedin Hospital

Date of Test
Iron
mg/L
Conductivity
mS/m
Copper
Mg/L
Saturation
Index
pH
TDS
mg/L
Legionella
HPC
(Pourplate)
Control Range Values
0 – 5
0 - 900
0 – 5
> 0  <3
7 – 11.5
<1000
<10
<100,000
Oct 03
0.17
89
0.10
1.94
8.84
710
<1
1,273
Nov 03
0.10
71
0.13
1.80
8.80
360
<1
1,561
Dec 03
0.06
62
0.10
1.77
8.77
480
<50
1,463
Jan 04
0.08
78
0.10
2.04
8.84
650
<10
10,010
Feb 04
<0.03
74
0.11
2.03
8.83
690
<10
11,730
Mar 04
0.03
79
0.15
2.04
8.84
730
<10
12,054
Apr 04
<0.34
84
0.37
1.99
8.79
790
<1
4,100
May 04
<0.10
90
0.29
2.06
8.86
770
<1
3,800
Jun 04
<0.30
80
0.24
1.78
8.78
59
<1
1,400
Jul 04
<0.03
45
0.09
1.83
8.35
320
<10
3,900
Aug 04
<0.04
61
0.13
1.98
8.55
490
<10
6,900

These results confirm the condenser water system is under good stable control.

 


A cost effective, single product, that is non toxic & maintenance free
90 DAY MONEY BACK GUARANTEE

Copyright Bio-cell (NZ Limited) © 2000 - All Rights Reserved
Tel:- +64 9 580 1567 Fax:- +64 9 525 6928 email:- sales@biosure.co.nz